Product Feature
- High expansion ratio
- Flexible tape, easy to operate
- Repeatable install
- environmental friendly and halogen-free formula
- Contains no fiber, non-toxic
- Contains no volatile organic compound
Application
- Fireproof sealing of all kinds of cables through cracks (firefighting)
- Fireproof sealing through the air duct(electricity)
- Fireproof sealing through plastic pipe (firefighting)
- Fireproof sealing of metal through-cable tunnel treatment(electricity)
Technical specifications
No. |
Performance |
Typical Value |
Test Standards |
|
1 |
Appearance |
Soft strip coils |
GB 23864-2009 5.3.2,6.1 |
|
2 |
Apparent density |
≤1.6×103 kg/m 3 |
GB 23864-2009 5.3.2,6.2 |
|
3 |
Water resistance |
3d,no swelling, nocracking |
GB 23864-2009 5.3.2,6.8 |
|
4 |
Alkali resistance |
3d,no swelling, nocracking |
GB 23864-2009 5.3.2,6.13 |
|
5 |
Acid resistance |
3d,no swelling, nocracking |
GB 23864-2009 5.3.2,6.12 |
|
6 |
Humidity resistance |
120h,no cracking, nopulverization |
GB 23864-2009 5.3.2,6.10 |
|
7 |
Freeze-thaw resistance cycle |
15 times,no cracking, no pulverization |
GB 23864-2009 5.3.2,6.11 |
|
8 |
Expansion character |
No flooding (or cement paste) |
≥10ml/g |
GB 23864-2009 5.3.2,6.14 |
After 48 hours of water immersed |
||||
After 48 hours of cement paste immersed |
||||
9 |
Flame retardation |
V-0 |
GB 23864-2009 5.1.4 |
|
10 |
Fire resistance |
Grade A3 or above |
GB 23864-2009 5.2,6.16 |
Direction for Use
1. Clean the hole, the debris around the perforation, dust, keep the sealing position dry and clean
2. Measure the size of the plugging position, calculate the appropriate length, and cut by hand。
3. The KC77-E fire retardant tape is tightly wound around the through-piece, which can be fixed with straps and pipe clips, and the winding is completed
Dimensions
Width×Thickness×Length:42mm×2.8mm×610mm