Features:
- 3 Cores Conductive Cable Breakout.
- Minimum shrink temperature: 110℃
- Minimum fully recovery temperature: 130℃
Technical properties
Test Items |
Test Method |
Test Requirements |
Tensile strength |
ASTM D 2671 |
12MPa min. |
Ultimate elongation |
ASTM D 2671 |
200% min. |
Volume resistivity |
ASTM D 257 |
104Ω.cm max. |
Water absorption |
ISO 62 |
1% max. |
Heat shock at 225℃/4hrs |
ASTM D 2671 |
No cracking, dropping |
Density |
ASTM D 792 |
1.0~1.1g/cm3 |
Selection table:
Size |
As supplied |
D (mm) |
I (mm) |
Recovered length |
Recovered wall(mm) |
|||||
(mm)±10% |
(mm)±10% |
±20% |
||||||||
(mm) |
l* |
f* |
a* (Min.) |
b* (Max.) |
a* (Min.) |
b* (Max.) |
L |
F |
Dw |
Iw |
HCB320-60/25 |
170 |
40 |
60 |
25 |
26 |
8 |
170 |
40 |
2.8 |
2.6 |
HCB330-80/ 38 |
210 |
50 |
80 |
38 |
34 |
16 |
215 |
55 |
3.5 |
3.2 |
HCB340-110/50 |
210 |
55 |
110 |
50 |
46 |
19 |
230 |
60 |
3.5 |
3.3 |
HCB350-125/57 |
220 |
60 |
125 |
57 |
55 |
20 |
240 |
68 |
3.5 |
3.2 |
a* = Inner diameter as supplied
b* = Inner diameter after fully recovered
l* = The length of L as supplied
f* = The length of F as supplied
Standard colors: Black